Troubleshooting
44
TROUBLESHOOTING CHART FOR Models FOR MODELS: 4007732; 6007732; 4007731; 6007731
*Also applicable to Models equipped with an electric intermittent pilot system. (Continued on next page)
1. Pilot will not stay lit
after following lighting
instructions.
A. Thermocouple producing
insufficient millivolts.
Check pilot flame – it must impinge on the thermocouple. The pilot flame may be low
or blowing (high) causing pilot to drop out. The pilot orifice or aerating hole may be
plugged (check for spiders, webs or other organic material). Be sure the thermocouple
is fully inserted in its bracket.
B. Loose or dirty
thermocouple
connection at gas valve.
Clean and/or tighten the thermocouple fitting at the connection to the valve.
C. Thermocouple defective.
Check thermocouple with millivolt meter – it should generate approximately 30
millivolts when not connected to a load. When connected to a load, it should generate
approximately 14 millivolts. If below 7 millivolts, replace.
D. Thermomagnet pilot
safety defective
Replace gas valve after above is checked out.
2. Main burner will not
come ON - pilot
burning and
thermostat set for
heat.
A. Gas valve not turned ON
after lighting the pilot.
Turn gas valve knob to the “ON” position - if no main gas flow, proceed to Step. "B".
B. Electric power to furnace
turned OFF.
Check for line voltage at furnace - if okay and no main gas flow, proceed to Step "C".
C. Low voltage transformer
or limit switch defective.
Check for 24 volts at the low voltage terminals of the transformer. If no voltage, turn
OFF electric power to furnace. Remove one wire from the limit switch and check for
continuity across both terminals. No continuity – replace the limit switch. With a good
limit switch back in the circuit and the electric power turned ON - if no voltage, replace
transformer.
NOTE: Before replacing the transformer or limit switch, check wiring for loose
connections or broken wires and repair as needed. If voltage is present at transformer,
proceed to Step "D".
D. Wall thermostat
defective.
With thermostat set for heat (contacts closed) check for voltage at the terminals on
gas valve. If no voltage is present replace defective thermostat.
NOTE: Before replacing thermostat, be sure to check the wiring from the furnace to
thermostat for loose connections or broken wires and replace as needed.
If voltage is present at the terminals on gas valve and still no gas flow to main burners,
proceed to Step "E".
E. Burner orifice plugged.
Clean or replace the orifice - if okay and still no gas flow to main burners, proceed to
Step "F".
Replace defective gas valve.
3. Burner comes "ON"
but goes OFF before
blower turns ON.
Turn OFF electric power to the furnace. Remove the top front panel, fan shroud and
blower wheel. Refer to Wiring Diagram and check all wiring inside the junction box.
Remove center front panel and check all wiring inside switch box containing fan, limit
and selector switches. Correct if necessary. If correct, proceed to Step "B".
NOTE: Selector switch used only on Models 5507331, 5507332, 6007731 &
6007732.
B. Defective limit switch.
If the burner goes OFF in less than five minutes from room temperature start, check
the limit control switch. If detective, replace.
NOTE: Blower should turn "ON" within three minutes after burner is "ON" from a room
temperature start. If not, proceed to Step "C”.
C. Defective motor (2-
speed).
Jumper across the fan switch, turn electric power ON, the motor should rotate. If a 2-
speed motor is used - jumper from "brown" terminal on the fan switch to #2 (red)
terminal on the selector switch, motor should rotate on "LOW" speed. Jumper from
same "brown" terminal on the fan switch to #3 (black) terminal on the selector switch,
motor should rotate on "HIGH" speed. Replace motor if defective.
D. Defective motor (1-
speed).
Jumper across the fan switch, turn electric power ON, motor should rotate. Replace
motor if detective.
If, after checking the above possibilities, problem still exists, replace the fan switch.
Comments to this Manuals